Correct using of the burner can not only prolong the service life of the burner, but also ensure the efficient and stable operation of the burner, and prevent the risk of illegal operation in the initial stage.
Turn on the power, start the burner motor, generate electric sparks between the ignition electrodes. After about 13 seconds of pre blowing, the oil pump solenoid valve opens automatically, and the oil mist emitted by the nozzle is ignited by the electric spark to form a flame. At this time, the flame detector senses the flame brightness and the controller enters the locked state.
nition electrode will delay ignition for about 5 seconds and stop ignition, and the burner will enter normal working state. If the ignition is not successful, no flame is formed, or the flame detector does not feel the flame brightness, after about 3 seconds of safety time, the safety alarm system acts, the start-up working procedure of the burner is cut off, and the red light is on.
When the burner is just started, if the flame detector has felt the brightness, the safety system will act, the controller will not enter the normal program, the solenoid valve will not open, the nozzle will not inject oil, after about 2 minutes of safety time, the fault red light will be on.
When starting the burner in the bright place, it is necessary to cover the flame detector first, and release the flame detector immediately after the burner sprays flame, otherwise the burner cannot work normally. When the red light of burner failure is on, press the reset button to restart the burner.