Possible reasons:
(a) It may be a voltage problem. Because the programmer has a low voltage protection function, the burner stops running when the input voltage is below 160 V (whichever the normal input voltage is 220-240 V). Later, when the voltage returns to normal, the burner starts again by itself.
(b) It may also be due to the insufficient supply pressure of the gas. When the burner starts to emit the flame, the pressure drops sharply, and the burner stops running when falling below the set point on the gas low-pressure switch. When the burner is stopped, the gas pressure rises, and when it rises above the set value on the low gas voltage switch, the burner restarts by itself. The reason for the sharp drop in gas may be the small caliber of the gas supply pipeline. If the fuel is LPG but supplied by the cylinder, note the number of cylinders connected. If the change of gas pressure is quite large, be particularly careful when adjusting the pressure on the gas low pressure switch.
(c) Please check whether the pressure adjusted on the gas low-pressure switch is incorrect.