Home Questions&Answers Technology Category

Preparation for debugging of oil-gas dual-use burner

Preparation for debugging of oil-gas dual-use burner
Jan 12, 2021 Category: Technology Category Page Views: 29 Author: EBICO Burner

Commissioning of gas supply pipeline

After the burner is installed, it is necessary to connect it to the air supply pipe network. The diameter of the gas supply pipe should meet the requirements of air supply, and the pressure loss should not exceed 5mbar. For the burner, when the diameter of the gas supply pipe is 1.5 or 40mm, the connection of the gas supply pipe of the burner should leave enough space to ensure the opening of the burner, so as to facilitate future maintenance work. Install the following components in sequence: 1. Ball valve; 2. Filter; (3A. Pressure regulating valve); 4. Double solenoid valve. If the gas pressure is higher than 500mbar, it is necessary to install a voltage regulator at the front of the pressure regulator valve to ensure that the gas pressure at the front of the pressure regulator valve is between 300-500mbar.

 

The following points should be noted when installing the components:

a.In order to avoid the gas pressure dropping too much when the burner is working, the distance between the pressure stabilizer valve and the double solenoid valve should not be more than 1.5 meters. The double solenoid valve is as close to the burner as possible, and the diameter of the pipe should not be less than 40mm.

b.All parts must be installed horizontally. If the double solenoid valve and the pressure stabilizer valve are installed vertically, the resistance of these parts will be increased.

c.Air tightness should be checked after all pipes are connected.

 

the inspection work before the start

a.Check whether the cables and wires are properly connected; Check the supply voltage, 380-400VAC, check all motor steering; Check whether each instrument works normally.

b.Disconnect the servo motor and check whether the damper mechanism and gas butterfly valve are flexible.

c.Check whether the photoelectric eye works normally. Check air tightness of heat conducting oil pipeline.

d.Start the heat conduction oil circulating pump, add the heat conduction oil of appropriate specifications as required until the oil shortage indicator is extinguished, check whether there is leakage in the heat conduction oil pipeline, and tighten it if necessary.

 

debugging of oil-gas dual-use burner

EBICO Burner answers the Preparation for debugging of oil-gas dual-use burner for you, to learn about the FAQ of EBICO Burner Technology Category. You can also learn more about other Technology Category FAQ about the EBICO Burner.
Need more information about EBICO please contact us
Need help?
Latest FAQ
More
Notes for dual - oil and gas burners
Jul 08, 2020 Category:
Latest News
More
Sep 26, 2023

How a bowl of Baixiang good noodles is born? About 1.8 million years ago, humans learned to cook food with purposeful control of fire. The use of fire has made unprecedented progress in human health and life, and Darwin also called cooking the most important invention of mankind after language....

Sep 22, 2023

Heat delivers real deliciousness. In recent years, China's kimchi industry has grown rapidly, with a market size of more than 40 billion. With the gradual rise of the "stay-at-home economy", Chinese compound condiments and prepared dishes have become new trends in the industry....

Burner Products
Based on the experience of optimization and integration of combustion technology resources in Europe, we have achieved a safe, energy-saving and environmentally friendly burner that can be adapted to all thermal equipment.
Innovation
EBICO's attitude of pursuing excellence and continuous improvement promotes the innovation of burner products in safety, energy saving, environmental protection and intelligence.
CSR
CSR
EBICO has always established a positive relationship with the environment, economy and society in order to fulfill its responsibilities as an enterprise.
Focus on burners and equipment to lead the global thermal industry.
欧保(中国)环境工程股份有限公司版权所有 苏ICP备20014131号-1
Online
Email
Inquire