- For the newly installed furnace, before commissioning, it is necessary to carefully test whether the gas and pressure meet the requirements of the burner; Check whether the testing instrument on the air supply pipeline is normal and whether the valve of the pipeline is open and closed normally, and whether it is convenient for future use and maintenance.
- For newly installed piping, all piping shall be carefully checked for installation reliability and piping tightness.
- Users using separate gasification stations should ensure that the air supply quantity and gas supply parameters meet the requirements of safe combustion.
- The operator should read the instruction carefully and master the safe operation knowledge and method.
- Check whether the gas valve is open before starting each time, otherwise the burner will not work (and will not alarm).
- Start the "running" button on the control cabinet. At this time, the digital display table will show the current temperature of water discharge, return and smoke exhaust of the furnace. The temperature of the new installation furnace is the ambient temperature.
- After the delay of boiler controller is about 1 minute, the relay of combustion engine is controlled to suck in, and the fan of combustion engine works for about 45 seconds to prepurge. If the burner fan does not work and does not alarm, check whether the low gas pressure switch is protected (if the BURNER rs38-50 on Riya Road should also check whether the plug cap is in good contact); Check whether the outlet temperature of boiler water meets the working requirements of boiler controller temperature parameters, that is, whether the outlet water temperature is lower than the set temperature.
- Combustion machine in advance after the purging throttle down to ignition, burning machine controller yellow lights flashing, ignition transformer discharge, about 2-3 seconds after gas solenoid valve open electricity, formed after the fire, flame detector detect flame and flame stability after combustion, ignition power transformer, secondary electro-magnetic valve or 2 fire on fire.
- When the combustion controller receives a signal that is not favorable to combustion (e.g., failed ignition, unstable air pressure, circuit problem), etc., the combustion controller will immediately turn off the gas and issue an alarm signal.
- If the combustion controller alarms, it must be manually reset by the operator after the fault is solved before it can continue to work.
- For the operation of the whole equipment, operators should refer to the furnace safety operation rules and production process requirements for operation.
- When the control temperature needs to be adjusted according to the production process requirements, the operator should refer to the intelligent NUMERICAL control table manual for adjustment.

EBICO Burner answers the Proper start up operation of burner for you, to learn about the FAQ of EBICO Burner Technology Category. You can also learn more about other Technology Category FAQ about the EBICO Burner.