- Before commissioning the newly installed furnace body, it shall carefully test whether the gas and pressure meet the requirements of the burner; Check whether the testing instrument on the air supply pipeline is normal and whether the valve of the pipeline is open and closed normally, and whether it is convenient for use and testing in the future.
- For newly installed pipelines, carefully check the installation reliability and sealing of all pipelines.
- Users using separate gasification stations should ensure that the air supply quantity and gas supply parameters meet the requirements of safe combustion.
- Operators should read the operating instructions carefully and master the knowledge and methods of safe operation.
- Check whether the gas valve is open before starting each time, otherwise the burner will not work (and will not alarm).
- Start the "Run" button on the control. At this time, the digital display table will show the current temperature of water discharge, return and smoke exhaust of the furnace.
- After the delay of the boiler controller is about 1 minute, the relay of the burner is controlled to suck in, and the burner fan works for about 45 seconds to prepurge; If the burner fan does not work and does not alarm, check whether the low gas pressure switch is protected; Check whether the outlet temperature of boiler water meets the working requirements of boiler controller temperature parameters, that is, whether the outlet water temperature is lower than the set temperature.
- After the pre-purge of the burner, the damper is closed for ignition, the yellow light of the burner controller flashes and the ignition transformer discharges. About 2-3 seconds later, the gas solenoid valve is energized and opens.
- When the combustion controller receives signals that are not favorable to combustion (such as failed ignition, unstable air pressure, circuit problem, etc.), the combustion controller will immediately turn off the gas and issue an alarm signal.
- If the combustion controller alarms, it must be manually reset by the operator after the fault is solved before it can continue to work.
- For the operation of the whole equipment, operators should refer to the furnace safety operation rules and production process requirements for operation.
- When the control temperature needs to be adjusted according to the production process requirements, the operator should refer to the intelligent NUMERICAL control table manual for adjustment.