FAULT ANALYSIS |
SOLUTIONS |
Ignition transformer malfunction. |
Replace ignition transformer. |
High voltage line connecting transformer to ignition line is damaged or loose. |
Replace the damaged spare parts. |
The insulating ceramic rod of the ignition wire has been broken. |
Replace the insulating ceramic rod. |
The gap between ignition rods is too wide or there is no gap. |
Adjust the gap between 4-5mm. |
The ignition rod rotates forward to touch the flame stabilizer. |
Make the distance between ignition rod and the flame stabilizer more than 10 mm. |
There is carbon slag in the gap of ignition rod. |
Clear carbon residue |
Improper distance between ignition rod end and front edge of nozzle. |
Adjust the distance between the ignition rod end and the front edge of the nozzle by about 3-4mm. |
Oil contains impurities, moisture, etc. |
Change oil or drain water. |
The setting angle of the damper is too large, flame is blown out. |
Try to gradually reduce the angle of the damper. |