FAULT ANALYSIS |
SOLUTIONS |
Short of oil(fuel) |
Add fuel |
Air in the oil pipe |
Exhaust the air in the pipe according to the exhaust procedure |
Solenoid coil short circuit |
Replace solenoid coil |
Oil pump damage |
Repair or replace |
Coupling is broken which connects motor and oil pump. |
Replace coupling |
The oil pump shall not rotate with the motor, the controller or the electric eye may be broken. |
Replace damaged parts |
The light in the combustion chamber is too strong (the refractory brick is burnt red or there is residual carbon slag burning, and the electric eye is abnormal). |
Burn out the carbon deposit, clean furnace |