After the servo motor drives the damper to the ignition opening state, the ignition transformer cuts in and outputs high voltage to the ignition electrode to produce the ignition spark. About 3 seconds later, the program controller sends power to the safety solenoid valve and the proportional solenoid valve. After the valve opens, the gas reaches the combustion head, mixes with the air provided by the fan, and then is ignited.