The main reasons are as follows
Cause of failure
here is too much air entering the furnace. Most of the reasons are the too large opening of the damper.
Solution
Reduce the opening of the burner damper and chimney damper, ignite the burner, and adjust the opening of the damper and damper to a proper angle after ignition.
Cause of failure
When the pressure of fuel oil is higher than that of atomized steam, ignition failure is easy to occur.
Solution
The problem can be solved by adjusting the fuel oil pressure to about 98kpa, which is lower than the pressure of atomized steam.
Cause of failure
Too low temperature or pressure of fuel oil causes ignition failure.
Solution
Increase the temperature or pressure of fuel oil.
Cause of failure
The fuel oil contains too much moisture, which causes difficulty or failure in ignition.
Solution
Dehydrate the fuel oil.
Cause of failure
Temperature or pressure of high pressure gas is too low.
Solution
Raise the temperature or pressure of gas.
Cause of failure
High pressure gas contains too much water.
Solution
Dehydrate elegant gas.
Cause of failure
Too much steam and too little fuel.
Solution
Turn down the steam valve and properly increase the fuel oil valve to achieve the proper oil steam ratio.