  • Q Cause analysis of severe vibration of burner’s blower fan

    A
    1. The fan shaft is not concentric with the electrode shaft.
    2. The rigidity of the foundation or the whole support is not enough.
    3. Loose impeller bolts or rivets and deformation of impeller.
    4. The impeller shaft disc hole is loosely matched with the shaft.
    5. The connecting bolts of casing, bearing seat and bracket, bearing seat and bearing cover are loose.
    6. The blade has dust, dirt, blade wear, impeller deformation and shaft bending, which makes the rotor unbalanced.
    7. Poor installation of the inlet and outlet pipes of the fan causes resonance.
  • Q Why there’s white smoke when the burner burns?

    A
    Cause of failure:
    a. The air volume is too small
    b. The air humidity is too high.
    c. The exhaust temperature is low.
    Solutions: (1) Turn down the damper. (2) Reduce the air volume appropriately and increase the inlet air temperature. (3) Take measures to increase the exhaust temperature.
  • Q What’s the precautions of cleaning burner filter?

    A

    The filter is used to filter out impurities and oil in the fuel gas to ensure the normal operation of the burner valve group. According to the quality of gas, the filter should be cleaned regularly. If wet gas is used, the air inlet valve can be closed periodically, the valve under the filter can be unscrewed, and the settled liquid can be discharged into a special container for dumping. Then, the upper cover can be removed, and the fastening screws of the filter screen can be loosened to remove the filter screen and the attached dirt. If clean dry gas is used, the cleaning cycle can be extended.

  • Q What are the Reasons for the Increase of Noise in the Work of Gas Boiler Burners?

    A
    The stop valve in the oil circuit is closed or the oil intake is insufficient, or the oil filter is blocked.
    The oil temperature at the inlet is too low, or the oil viscosity is too high, or the temperature in the oil pump is too high.
    Oil pump damage
    The blower motor bearing damaged
    The blower impeller is too dirty
  • Q How to Deal with the Increase of Noise in the Work of Gas Boiler Burners?

    A

    (1) Check whether the valve in the pipeline is open and whether the oil filter is working normally, and clean the filter screen of the oil pump

    (2) Raise or lower the oil temperature

    (3) Replace the oil pump

    (4) Replace the motor or bearings

    (5) Replace the blower impeller

  • Q What tests should be carried out in the hot state of boiler after overhaul?

    A 1. Adjustment test of pulverized coal fineness
    2. Adjustment test of power consumption of pulverizing
    3. Air leakage rate test of air preheater
    4. Dust collector efficiency test
    5. Combustion adjustment and boiler efficiency test
    6. Flow rate, pressure head, power and efficiency test of all kinds of improved fans (or pumps)
  • Q What happened when excessive carbon monoxide (CO) was produced during combustion?

    A Possible reasons:
    a. Too much or too little combustion air.
    b. If the burner has been used for a long time, please check the air nozzle for blockage.
    c. Please pay attention to whether the supply of fresh air in the furnace room is sufficient.
  • Q Why is the resistance in the furnace too high?

    A Possible reasons: (The following reasons refer to what happens when the burner is used in the positive pressure furnace of the boiler)
    a. It may be that the internal pressure of the furnace itself is too high.
    b. It may also be that the diameter of the smoke exhaust pipe is too small or there are too many turns. At the same time, please check whether the smoke exhaust passage is blocked. If a chimney baffle is installed, please pay attention to whether it has been opened. If the resistance in the furnace is too high, it will make a vibration noise when it catches fire. In addition, if the pressure of gas is too high, it will make a special noise when it catches fire.
  • Q Reasons for noise of high-pressure fuel pump of burner in asphalt mixing building

    A (1) The fuel pipe diameter is too small.
    (2) Air is mixed into the fuel pipe.
    (3) Contamination of oil filter
    (4) The distance between the oil tank and the burner is too large or there is external leakage.
  • Q What’s the precautions for burner installation

    A 1. The controller must be installed in a ventilated environment.
    2. The ventilation openings in the suction grid part and the installation space cannot be blocked ornarrowed.
    3. There should be no explosion or firepossibilitieson the installation site.
    4. Before installation, the internal space of all fuel delivery pipelines shall be carefully cleaned.
  • Q Why is the burner fan surging when the boiler is ignited?

    A When igniting, the flame oxygen content is too low, which leads to unstable combustion, and the burner will surge when running at low load, which can be solved by increasing the air volume.
  • Q The burner motor is running, and the voltage is applied to the terminal of the controller, and there is no ignition. Why does it stop working?

    A 1. The distance between ignition electrodes is too long, adjust the electrode spacing.
    2. The equipment is polluted,needs to be
    3. The ignition electrode or circuit is grounded, to eliminate other connections and replace the damaged electrode or cable.
    4. If the ignition transformer fails, replace it.
EBICO and the international Novar Bergamo and Vizcaya team work hand in hand to optimize the fusion of Europe's cutting-edge low-carbon and low-NOx combustion technologies to form EBICO's top technology strategy system. The company has strategic partners or factories in Italy, Germany, Switzerland, Holland, China, the products have been involved in Europe, Asia, Africa and other continents...

QUICK LINK

About EBICO

RESOURCES

PRODUCTS

CONTACT US

  +86-18900630022
 +86-510-85187552
  +86-18921341492 
   info@ebico.com
   #48 Building,No.58 Xiuxi Road,Binhu District, Wuxi, Jiangsu, China
Copyright © 2025 EBICO(CHINA) Environment Co., Ltd. All rights reserved. Sitemap Privacy Policy